Effect of ERV on AC Run Time
My colleague and I had a recent discussion about his ongoing project. We focused on figuring out how adding an Energy Recovery Ventilator (ERV) to treat ventilation air impacts the run time of air conditioning equipment. To answer this, we used adicot.com's Psychrometric Chart 2-Condition Calculator and the methodology shown below to compare equipment run times with untreated ventilation air versus ventilation air treated by an ERV. In this example, the run time spent conditioning the ventilation air dropped by about 25%. You'll find the details of our approach in the following section.
To solve this problem, we assumed the following will be given:
Given:
-
Equipment Cooling Capacity [BTU/h] provided by the manufacturer
-
ASHRAE Outside air design temperatures (Dry bulb and wet bulb) [°F]
-
Coil Leaving Air Temperatures (Dry bulb and wet bulb) [°F] provided by the manufacturer
-
Ventilation air volume [cfm] per ASHRAE 62.1 or the building code
Procedure:
-
Calculate the Ventilation Air Total Cooling Load [BTU/h] (Psychrometric Chart 2-Condition Calculator)
-
Run time = Ventilation load/Equipment Capacity x 60 min [min]
Example:
-
Equipment Cooling Capacity: 2.50 tons or 30,000 BTU/h
-
Outside air temperatures in Boston, MA: 88 °F / 72 °F
-
Coil Leaving Air Temperatures: 55 °F / 54.9 °F
-
Ventilation air volume: 100 CFM
-
Calculate the total load of ventilation air using Psychrometric Chart 2-Condition Calculator where:
-
Entering Conditions are outside air design temperatures
-
Exiting Conditions are coil-leaving air temperatures
Ventilation Air Total Cooling Load = 5,274 BTU/h
- Run time = 5,274 BTU/h / 30,000 BTU/h x 60 min/hr = 10.5 minutes/hour to condition the ventilation air
Adding an ERV: Replace outside air temperature with the ERV leaving air temperature (100 CFM @ 78 °F dry bulb, 68 °F wet bulb):
-
Total Load: 3,940 BTU/h
-
Run time: 7.9 minutes/hour to condition ventilation air
On the psychrometric chart, the example looks like this. The coil cools the ventilation air along a line down to the coil leaving condition. Starting from the outdoor air, that line is long; starting from the air leaving the ERV, it is shorter, and the load is smaller in proportion to the drop in enthalpy along it.
Move the pointer over the chart to read the air properties at a point.
- Outdoor air (88 / 72 °F) and air leaving the ERV (78 / 68 °F)
- Air leaving the coil (55 / 54.9 °F)
- Relative humidity, %
- Wet bulb, °F
- Enthalpy, Btu/lb
- Specific volume, ft³/lb
In this example, the ERV cut the run time spent on ventilation air by about 25%. Your result depends on the climate, the airflow and the ERV's leaving-air condition.