International Energy Conservation Code Window U-Factors & SHGC Default Values
For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms
Calculator help
Hi! Ask me anything about using this calculator: what an input means, where to find a value, or why you got a result.
An AI assistant (Claude) that reads this page. It can make mistakes: check important numbers, and confirm design decisions with a licensed engineer.
Building in Florida? See our engineering services in Florida.
Methodology
NFRC U-factor and SHGC values are critical when performing cooling load calculations and energy code compliance calculations. New windows have these values on their NFRC labels. Where the windows no longer have an NFRC label, the International Energy Conservation Code (IECC) and the Florida Energy Conservation Code (FECC) provide default U-factor, SHGC and VT values. The values below are taken directly from the 2024 International Energy Conservation Code and the 2023 Florida Building Code, Energy Conservation (8th edition), Tables C303.1.3(1), (2) and (3); the two codes give identical values, unchanged from the 2021 IECC and 2020 FBC.
Table C303.1.3(1): default glazed fenestration U-factors
| Frame type | Single pane | Double pane |
|---|---|---|
| Metal | 1.2 | 0.8 |
| Metal w Thermal Break | 1.1 | 0.65 |
| Nonmetal or Metal Clad | 0.95 | 0.55 |
| Glazed Block | 0.6 | 0.6 |
| Skylight - Metal | 2 | 1.3 |
| Skylight - Metal w Thermal Break | 1.9 | 1.1 |
| Skylight - Nonmetal or Metal Clad | 1.75 | 1.05 |
Table C303.1.3(2): default opaque door U-factors
| Door type | U-factor |
|---|---|
| Insulated Metal (Other) | 0.6 |
| Insulated Metal (Rolling) | 0.9 |
| Insulated, nonmetal edge, max 45% glazing, any glazing double pane | 0.35 |
| Uninsulated Metal | 1.2 |
| Wood | 0.5 |
Table C303.1.3(3): default window, glass door and skylight SHGC and VT
| Glazing | SHGC | VT |
|---|---|---|
| Single Pane, clear | 0.8 | 0.6 |
| Single Pane, tinted | 0.7 | 0.3 |
| Double Pane, clear | 0.7 | 0.6 |
| Double Pane, tinted | 0.6 | 0.3 |
| Glazed block | 0.6 | 0.6 |
Examples
Example 1: you are performing a load calculation for an existing building. On a site visit you see that the existing windows have metal frames and single-pane glass with no tinting. What are the code default U-factor, SHGC and VT for the windows?
- Find the U-factor from Table C303.1.3(1) by looking up metal frame, single pane: U-factor = 1.2
- Find the SHGC and VT from Table C303.1.3(3) by looking up single pane, clear: SHGC = 0.8, VT = 0.6
Example 2: on the same site visit you see that the existing doors are uninsulated metal. What is the code default U-factor?
- Find the U-factor from Table C303.1.3(2) by looking up uninsulated metal: U-factor = 1.2
To solve both examples with the lookup above, choose Metal, Single, Clear and Uninsulated Metal, or choose “Show an example” on each tab.
Where the actual product can't be identified, the code defaults are a reasonable starting point; they can understate the solar gain of clear glass.