Cooling Load Ballpark Estimator: Tons per Square Foot

Methodology

The calculator estimates a building's occupants, lights and other electrical load, and refrigeration (cooling) from its floor area and building type, using check figures of what buildings of each type have historically had:

  • Occupants = floor area ÷ floor area per person
  • Lights and other electrical = floor area × watts per square foot
  • Refrigeration = floor area ÷ floor area per ton, and 1 ton = 12,000 Btu/h (3.52 kW)

The results give a low, average and high estimate for building types whose figures span a range, and only an average for the others. Low refrigeration corresponds to the most square feet per ton.

In metric units, the same figures are converted to square meters (1 ft² = 0.092903 m²).

Example. For a 10,000 ft² general office building, the calculator gives 35.7 tons (428,571 Btu/h) of refrigeration on average, with a range of 27.8 to 52.6 tons, and 25,000 W of lights and other electrical on average.

What it is for

This is a pre-design ballpark: an estimate of the cooling load before a full analysis has been done, or a sanity check of a load calculation's result. It is not a load calculation. The check figures take no account of the inputs a load calculation uses, such as construction, climate, orientation, glazing or ventilation. As buildings, lighting and equipment become more efficient, the watts and tons trend lower than these historical figures.

For a quick look at a single space, the coil selection calculator and the psychrometric calculator work from airflows and air conditions. For a full load calculation, see our cooling load/heat load calculation services.