Cooling Load Ballpark Estimator: Tons per Square Foot
Calculator help
Hi! Ask me anything about using this calculator: what an input means, where to find a value, or why you got a result.
An AI assistant (Claude) that reads this page. It can make mistakes: check important numbers, and confirm design decisions with a licensed engineer.
Step-by-step guide: How to Use the Cooling Load Ballpark Estimator
Methodology
The calculator estimates a building's occupants, lights and other electrical load, and refrigeration (cooling) from its floor area and building type, using check figures of what buildings of each type have historically had:
- Occupants = floor area ÷ floor area per person
- Lights and other electrical = floor area × watts per square foot
- Refrigeration = floor area ÷ floor area per ton, and 1 ton = 12,000 Btu/h (3.52 kW)
The results give a low, average and high estimate for building types whose figures span a range, and only an average for the others. Low refrigeration corresponds to the most square feet per ton.
In metric units, the same figures are converted to square meters (1 ft² = 0.092903 m²).
Example. For a 10,000 ft² general office building, the calculator gives 35.7 tons (428,571 Btu/h) of refrigeration on average, with a range of 27.8 to 52.6 tons, and 25,000 W of lights and other electrical on average.
What it is for
This is a pre-design ballpark: an estimate of the cooling load before a full analysis has been done, or a sanity check of a load calculation's result. It is not a load calculation. The check figures take no account of the inputs a load calculation uses, such as construction, climate, orientation, glazing or ventilation. As buildings, lighting and equipment become more efficient, the watts and tons trend lower than these historical figures.
For a quick look at a single space, the coil selection calculator and the psychrometric calculator work from airflows and air conditions. For a full load calculation, see our cooling load/heat load calculation services.