Condensate Rate Calculator

For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms

For a single condition, use the psychrometric chart calculator. To convert condensate between units, use the condensate converter.

Methodology and equations

This calculator can be used in US or Metric Units. The user inputs leaving and entering coil conditions as Dry Bulb or Dew Point Temperature, Wet Bulb Temperature or Relative Humidity, coil Airflow rate, and project altitude. The formulas to calculate the psychrometric properties of the initial and final conditions are based on the methodology outlined in the ASHRAE 2021 Handbook. The change in the humidity ratio is used to calculate the Condensate Generated.

lb,moisture/hr = Q / v x Δw x C

where: Q = air flow rate, CFM

v = specific volume of the entering air, ft³/lb dry air

Δw = change in humidity ratio, w,entering − w,leaving, lb,moisture/lb,dry air

C= 60 min/ hr

The following conversions are used to calculate the various units of condensate generated :

BTU/h = Pints/day x 1.04 lb/pint / 24 hrs/day x 1055 BTU/lb

1 kW = 3412.142 BTU/hr

1 kW = 1000 W

1 Gallon = 8 pints = 3.78541 liters

1 Gallon of water = 8.34 lbs

How the calculator solves

Every property uses the 2021 ASHRAE Handbook, Fundamentals ch. 1 equations directly, solved iteratively (no chart reading or simplified fits). Saturation pressure uses the Hyland-Wexler equations (5 and 6), over ice below 32 °F and over water above. Humidity ratio comes from the wet bulb by equation 35 (or 37 when the wet bulb is below freezing), or directly from the vapor pressure when the RH or the dew point is given. Dew point and wet bulb are solved iteratively: the dew point starts from ASHRAE's equation 39 or 40 and is refined by Newton's method until it matches the saturation pressure, and the wet bulb is solved from equation 35 or 37 the same way. Altitude sets the atmospheric pressure by equation 3. The 2025 Handbook replaces the Hyland-Wexler saturation pressure with the IAPWS formulations (IAPWS-IF97 over water, IAPWS 2008 over ice); from −20 to 150 °F the two agree within 0.03 %, below the precision of most results shown.

Top