Vapor Pressure Deficit (VPD)

Feedback on this calculator?

Your current inputs are sent with it, so we can see what you saw.

Reading the chart

The chart plots relative humidity against room temperature and colors it in bands of VPD. The cross-hair marks the room you entered, and the band it sits in is outlined in the key. Each boundary between bands is a line of constant VPD, so moving along one changes the temperature and humidity without changing the VPD: a warmer room at a higher humidity can hold the same VPD as a cooler, drier one, which is often the cheaper condition to maintain in a hot, humid climate.

With no leaf temperature, the bands show the air VPD. With one, they show the leaf VPD for a leaf that many degrees cooler or warmer than the room, and a further band appears where a cooler leaf would be below the room's dew point and water would condense on it.

The bands break at 0.4, 0.8, 1.2 and 1.6 kPa, the ranges growers commonly quote for cuttings and seedlings, vegetative growth, and flowering. They are a guide to reading the chart, not a recommendation: the right VPD depends on the crop and its stage, so take your target from your grower or crop guidance.

What vapor pressure deficit is

Vapor pressure deficit (VPD) is the difference between how much water vapor the air could hold when saturated and how much it holds now, expressed as a pressure. It is a direct measure of the air's drying power: a high VPD means the air is relatively dry and pulls moisture from surfaces and plants quickly; a low VPD means the air is close to saturation. Growers use VPD to manage transpiration in grow rooms and greenhouses, and HVAC designers use it to size dehumidification for them.

Equations

Air VPD = pws(Tair) − pw

Leaf VPD = pws(Tleaf) − pw

where pws(T) is the saturation vapor pressure at temperature T (the Hyland-Wexler equations of the 2021 ASHRAE Handbook, Fundamentals, chapter 1), and pw is the partial pressure of the water vapor in the air. With the relative humidity known, pw = RH × pws(Tair). With the wet bulb known, the humidity ratio W comes from ASHRAE's wet-bulb equation (eq. 35, or eq. 37 with ice on the wick below 32 °F) and pw = p × W ÷ (0.621945 + W). A band boundary on the chart is the same equation solved for the humidity: RH = (pws(Tleaf) − VPD) ÷ pws(Tair), with Tleaf = Tair when no leaf temperature is entered. The dew point is the temperature at which pws equals pw, solved exactly. These are the same exact ASHRAE psychrometrics as the psychrometric calculator, and they hold below freezing too. Pressures are converted from psia to kPa by 6.89476. The 2025 Handbook replaces the Hyland-Wexler saturation pressure with the IAPWS formulations (IAPWS-IF97 over water, IAPWS 2008 over ice); from −20 to 150 °F the two agree within 0.03 %, so the results are unchanged at the precision shown.

Example: a grow room at 77 °F and 55 % RH, with leaves at 75 °F. The saturation vapor pressure at 77 °F is 3.169 kPa. The vapor pressure in the air is 0.55 × 3.169 = 1.743 kPa, so the air VPD is 3.169 − 1.743 = 1.43 kPa. The saturation pressure at the 75 °F leaf is 2.965 kPa, so the leaf VPD is 2.965 − 1.743 = 1.22 kPa. The dew point is 59.6 °F and the wet bulb 65.6 °F.