Condensate Pump Size Calculator

For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms

Methodology

Condensate generated

The condensate is the moisture the coil removes from the air:

Condensate (lb/h) = Airflow (cfm) × 60 ÷ v × (Wentering − Wleaving) ÷ 7000

where v is the specific volume of the entering air (ft³/lb) and W the humidity ratio in grains per pound, each from the dry-bulb and wet-bulb temperatures and the altitude, using the psychrometric equations of the ASHRAE Handbook (Fundamentals). One gallon of condensate weighs about 8.345 lb, so gph = lb/h × 0.11983. This is the same calculation as our condensate calculator.

Pump selection

A pump suits the job when it is made for the application and the voltage, and its flow at the head height is at least the condensate flow. Manufacturers rate condensate pumps at a few heads only, so between those heads the calculator takes the pump's flow at the next higher listed head, which is conservative. Above a pump's highest listed head it is not rated, and is not listed.

Condensate pumps run on a float switch: the pump starts when the reservoir fills and stops when it empties. A pump with more capacity than the condensate simply runs for shorter periods, so any larger pump would also work. The calculator shows only the smallest pump that does the job, since it is usually the quietest and least expensive, and says how many larger pumps also fit.

Example

A coil cooling 1,200 cfm from 80 °F dry bulb, 67 °F wet bulb to 55 °F dry bulb, 54 °F wet bulb, at sea level, makes about 13.2 lb/h, or 1.6 gph, of condensate (choose Show an example in the calculator to load it). For an air conditioner at 115 V with a 10 ft lift, 12 Little Giant pumps qualify, and the best fit is the VCMA-15 at 25 gph at 10 ft, sold as four models (VCMA-15UL, -15ULS, -15ULST and -15ULT). The VCL-24 models are rated only up to 9 ft, so they drop out at a 10 ft lift.

Notes

  • The pump data are Little Giant's catalog ratings. Confirm the selection, the reservoir size and any safety-switch wiring with the manufacturer's data. Adicot is not affiliated with Little Giant or any other equipment manufacturer.
  • Each application and voltage has a highest head the catalog rates its pumps at; the calculator shows it under the head height and lists no pump above it.
  • Size the discharge line and allow for its friction: long or small-diameter tubing adds to the effective head.
  • Hi-temperature models are for plenum applications and condensing appliances with hot condensate; check the maximum liquid temperature for your equipment.