Equipment Heat Gain Calculator

For use by professionals. No warranty; confirm results and design decisions with a licensed engineer. Site Terms

Methodology, equations and example

Equipment adds heat to a room in two ways. Sensible heat warms the air, partly by convection, which the air picks up at once, and partly by radiation, which the walls, floor and furniture absorb first and give back to the air over the following hours. Latent heat is moisture, from steam, boiling water or wet dishes, and is a load on the cooling coil as soon as it is released.

The calculator looks up each item's heat gain in the ASHRAE Handbook, Fundamentals (2025), Chapter 18, applies the quantity, diversity and hours you enter, and converts the hour-by-hour heat gain into cooling load with the radiant time series (RTS) method of the same chapter.

Where the heat gain comes from

  • Computers, monitors, printers and office equipment (Tables 11 to 13): measured peak power, the highest 15-minute reading, in watts. Nameplate ratings are not used: office equipment typically draws 25 to 50 % of its nameplate.

  • Office plug load by floor area (Table 14): watts per square foot for a whole office, already allowing for diversity and one printer per 8 to 10 desks.

  • Kitchen appliances (Tables 8A to 8E): unhooded electric appliances give radiant, convective and latent heat to the room, ready to cook (idle) or cooking. Under a working exhaust hood, only the radiant heat reaches the room; the hood takes the convective and latent heat away. For a hooded appliance with a known rated input, the radiant gain is q = rated input × FU × FR (Equation 5), with the table's usage factor FU and radiation factor FR.

  • Idle or cooking: kitchen appliances are typically on all day but cook less than 25 % of the time, so ASHRAE takes the idle (ready to cook) heat gains as a good estimate for the cooling load. That is the recommended choice. For an idle appliance that will cook during some hours, such as a lunch rush, enter the share of each of those hours it spends cooking. In those hours its radiant, convective and latent gains are each idle + share × (cooking − idle), from Tables 8A and 8B, a time-weighted blend within the hour; this blend is the calculator's method, not an ASHRAE rule.

  • Unhooded, from rating: the unhooded tables leave out some electric appliances, such as the full-size convection oven, that Table 8C lists under a hood. For those the calculator estimates the unhooded heat gain from the Table 8C factors: unhooded, all of the appliance's idle energy, rated input × FU, reaches the room, FR of it as radiant. Table 8A's own figures follow the same relation (the microwave/convection rapid-cook oven: 19,400 × 0.20 = 3,880 Btu/h against 3,900 printed). This is the calculator's estimate, not an ASHRAE value, and it has no moisture: add the moisture from food cooked or dried as an Other row.

  • Dishwashing and pre-rinse equipment (Table 8F): sensible and latent heat to the room. Hooded and ducted machines list only the share that reaches the room.

  • Medical and laboratory equipment (Tables 9 and 10): the peak measured power. ASHRAE notes that this equipment varies too widely to generalize, so use the manufacturer's data where you have it (and always for large equipment such as MRI).

  • Electric motors (Equations 2 to 4), from the motor horsepower and efficiency:

    • Motor and the machine it drives both in the room: q = 2545 × hp ÷ EM
    • The machine in the room, the motor outside: q = 2545 × hp
    • The motor in the room, driving a fan or pump outside it: q = 2545 × hp × (1 − EM) ÷ EM

    If the efficiency box is left blank, the calculator uses the minimum full-load efficiency for the motor's size, poles and enclosure from ASHRAE Standard 90.1 (Handbook Tables 7A and 7B), rounding a size between two listed ones as footnote b of Table 7A says. Motor heat is split half radiant and half convective. Use and load factors are taken as 1, as the Handbook advises unless the motor's duty is known.

  • Other equipment: a measured or peak wattage; a nameplate wattage, of which ASHRAE suggests 50 % as conservative and 25 % as more nearly correct (100 % for a resistance heater); or a sensible and latent heat gain you already know.

Radiant share

Where the Handbook gives a radiant share, the calculator uses it: 10 % for desktop computers, 25 % for laptops and docking stations, 40 % for monitors, 30 % for printers and copiers, 50 % for motors, and the measured split for kitchen appliances. Where it gives none (tablets, the miscellaneous office equipment of Table 13, medical and laboratory equipment), it uses the office equipment split of Table 17: 10 % radiant for equipment with a fan or compressor, 30 % without. Each row's radiant box shows the share used, and you can enter another.

Quantity, diversity and schedule

Each row's heat gain is multiplied by the quantity and the diversity, the share of the items running at once. Diversity is 100 % unless you enter a figure. For a large open office, ASHRAE Table 15 gives 75 % for desktop computers, 70 % for laptop docking stations, 75 % for notebooks, 70 % for screens and 45 % for printers; a small office with one or two people usually has no diversity. The row's note shows the Table 15 figure where there is one.

The equipment runs from the On at hour to the Off at hour. Each hour is the hour starting at that time, so 8 am to 5 pm is nine hours, the last one 4 to 5 pm. Equal times mean the equipment runs all day. A schedule past midnight wraps to the next morning.

From heat gain to cooling load

For each hour of the design day, the convective part of the heat gain is load at once. The radiant part becomes load over the next 24 hours, by the nonsolar radiant time factors r0 to r23 of Table 22 for the room's construction, floor and glass:

Qr,θ = r0 qr,θ + r1 qr,θ−1 + r2 qr,θ−2 + … + r23 qr,θ−23 (Equation 33)

The design day repeats, so the hours before midnight carry the previous evening's gains. The sensible cooling load is the convective gain plus Qr. Latent load is immediate. The calculator reports the hour with the highest sensible load, or any hour you choose, so it can be added to a load calc at its design hour.

If your load program does its own radiant time series, enter the sensible heat gain with its radiant share, and the latent gain, from the results table, rather than the cooling load. Adding the cooling load to a program that delays it again would delay the radiant part twice.

Example: An office suite has six desktop computers and twelve monitors on 8 am to 5 pm, one monochrome printer on the same hours, a coffee brewing urn kept hot from 7 am to 2 pm, a refrigerator on all day, and a microwave used from noon to 1 pm. The room is medium construction, carpeted, with 50 % glass.

  • Desktops: 6 × 82 W × 3.412 = 1,679 Btu/h, 10 % radiant (168 Btu/h).
  • At noon they have run for 5 hours, so their radiant gain has been converted at r0 + … + r4 = 49 + 17 + 9 + 5 + 3 = 83 %: 168 × 0.83 = 139 Btu/h. With the 1,511 Btu/h convective, their load at noon is 1,650 Btu/h.
  • The microwave adds 822 W × 3.412 = 2,805 Btu/h for that hour; with its radiant part delayed, 2,662 Btu/h of load.
  • The urn, from Table 8A, gives 200 Btu/h radiant, 300 Btu/h convective and 700 Btu/h of moisture while it is on.
  • All six rows together peak at noon at 7,510 Btu/h sensible and 700 Btu/h latent, though their sensible heat gain with everything on would be 7,795 Btu/h: part of the radiant heat is still in the room's mass.

Limits of this calculator

  • The heat gains are the Handbook's typical measured values. A specified product's data is better: use the Other rows for it.
  • The radiant time factors are ASHRAE's for three representative zones (Table 24). For a room that is not reasonably similar, the heat balance method or custom factors are more accurate.
  • Hooded appliances assume a hood that captures and contains the plume at its design exhaust rate. A hood that does not spills convective and latent heat into the kitchen.
  • The tables are for air-based cooling. ASHRAE has not published radiant time factors for radiant cooling systems.