Duct Sizing Chart

Round and rectangular duct airflow at 0.08 and 0.10 in. wg per 100 ft.

Each figure is the most air the duct carries at or below the friction rate at the top of its column, from the Duct Size Calculator's own model, rounded down to the nearest 5 cfm. Velocity in fpm is under or beside each airflow.

Basis: standard air, inside dimensions, straight duct, friction per 100 ft. Fittings, joints, liner and installation are not included. Flex that sags or is compressed carries less air than shown. For any other size, airflow, friction rate or material, use the calculator.

Round duct

Maximum airflow, cfm (velocity, fpm), by round duct inside diameter
Round ductMetalFlex
0.08 in. wg0.10 in. wg0.08 in. wg0.10 in. wg
4 in.30 (344)35 (401)20 (229)25 (286)
5 in.60 (440)65 (477)40 (293)50 (367)
6 in.95 (484)110 (560)70 (357)80 (407)
7 in.145 (543)165 (617)110 (412)120 (449)
8 in.210 (602)240 (688)155 (444)175 (501)
9 in.290 (656)330 (747)215 (487)240 (543)
10 in.385 (706)435 (798)290 (532)320 (587)
12 in.630 (802)710 (904)470 (598)525 (668)
14 in.950 (889)1075 (1006)710 (664)795 (744)
16 in.1360 (974)1535 (1099)1015 (727)1140 (816)
18 in.1860 (1053)2095 (1186)1390 (787)1560 (883)
20 in.2460 (1128)2775 (1272)1845 (846)2065 (947)
22 in.3165 (1199)3570 (1352)2375 (900)2660 (1008)
24 in.3990 (1270)4495 (1431)2995 (953)3350 (1066)
26 in.4930 (1337)5555 (1507)3705 (1005)4145 (1124)
28 in.5995 (1402)6755 (1580)4505 (1054)5045 (1180)
30 in.7195 (1466)8105 (1651)5410 (1102)6055 (1234)
32 in.8535 (1528)9605 (1720)6420 (1149)7185 (1286)
36 in.11640 (1647)13105 (1854)8770 (1241)9815 (1389)

Rectangular metal duct

Find the short side down the left and the long side across the top. A rectangle is charted at its circular equivalent (Huebscher), which carries the same air at the same friction rate; it is not the rectangle of the same area, which would be too small. Shapes over 4:1 are left blank.

Galvanized metal at 0.08 in. wg per 100 ft: maximum cfm, with velocity in fpm below
Short × long, in.68101214161820243036
6125500180540240576305610365626430645495660560672690690
827060836064846069055571465573776076086077410657991380828
1049070662575076578790581510458361190857148589119359292385954
1280080098084011658741355903154592719359682535101431351045
141205885144092616809601920987241510353170108739401126
1617259702010100523101040291010913840115247901198
182355104727051082342511424540121156751261
2031151121395511875260126265951319
24505012636755135185101418
Galvanized metal at 0.10 in. wg per 100 ft: maximum cfm, with velocity in fpm below
Short × long, in.68101214161820243036
6140560205615275660345690415711485728560747630756780780
830568641073852078063081074083385585597087312059041555933
10555799705846860885102091811809441345968167510052180104626901076
12905905110594713159861530102017451047218510932855114235351178
141360999162510451895108321651113272011663575122644401269
16194510942270113526001170328012304330129953951349
182655118030501220386012875115136463901420
2035101264445513375925142274251485
24569014237605152195851598

How to read it

Choose the friction rate first. 0.08 to 0.10 in. wg per 100 ft is common for low-velocity comfort ductwork, but noise or the fan's available static pressure often governs. Then check the velocity: the design criteria on the calculator page give the usual ranges for supply, return and main trunks.

These charts are an estimating aid and do not replace engineering judgment.